Connecting The Converter To Profinet - Siemens SINAMICS G115D Operating Instructions Manual

Distributed drive
Hide thumbs Also See for SINAMICS G115D:
Table of Contents

Advertisement

Table 4- 2
EtherNet/IP protocols
Protocol
Port
number
Implicit mes-
2222
saging
Explicit mes-
44818
saging
Table 4- 3
Connection-oriented communication protocols
Protocol
Port
number
ISO on TCP
102
(according to
RFC 1006)
SNMP
161
Simple Network
Management
Protocol
Reserved
49152 ...
65535
4.13.4

Connecting the converter to PROFINET

Procedure
1. Integrate the converter in the bus system (e.g. ring topology) of the control using PROFINET
cables and PROFINET sockets X150 P1/P2.
The maximum permitted cable length from the previous station and to the next one is
100 m.
2. Externally supply the converter with 24 V DC through interface X01.
You have now connected the converter to the control system via PROFINET.
SINAMICS G115D distributed drive
Operating Instructions, 09/2020, FW V4.7 SP13, A5E48681219B
Layer
Function/description
(2) Link layer
(4) Transport layer
(4) UDP
Used for exchanging I/O data.
This is inactive when delivered. Is activated when selecting Ether-
Net/IP.
(4) TCP
Used for parameter access (writing, reading).
(4) UDP
This is inactive when delivered. Is activated when selecting Ether-
Net/IP.
Layer
Function/description
(2) Link layer
(4) Transport layer
ISO-on-TCP protocol
(4) TCP
ISO on TCP (according to RFC 1006) is used for the message-oriented
data exchange to a remote CPU, WinAC or devices of other suppliers.
Communication with ES, HMI, etc. is activated in the factory setting,
and is always required.
(4) UDP
Simple network management protocol
SNMP enables network management data to be read out and set
(SNMP managed objects) by the SNMP manager.
It is activated in the factory setting, and is always required
(4) TCP
Dynamic port area that is used for the active connection endpoint if
the application does not specify the local port.
(4) UDP
Cables and connectors (Page 57)
4.13 Connecting to PROFINET and Ethernet
Wiring
77

Advertisement

Table of Contents
loading

Table of Contents