Siemens SINAMICS G115D Operating Instructions Manual page 174

Distributed drive
Hide thumbs Also See for SINAMICS G115D:
Table of Contents

Advertisement

Advanced commissioning
6.8 Conveyor technology control functions
Note
The motor will have the following behavior with the end position shutdown (p3392 = 1) and
level-triggered sensor signals (p3394 = 1 or 2) activated:
• Once a stop sensor at the positive or negative position is triggered, the motor stops even if
the level is canceled.
• Once a stop sensor at the center position is triggered, the motor stops; if the level is
cancelled, then the motor runs again.
Parameters
You can commission the conveyor technology functions via the Startdrive PC tool.
172
Conveyor technology control parameters (Page 175)
Operating Instructions, 09/2020, FW V4.7 SP13, A5E48681219B
SINAMICS G115D distributed drive