Additional information on the SIMOGEAR geared motor
11.2 Specific data motor
Figure 11-7
11.2.10.3

Terminal marking

For terminal designations, the following principle definitions apply to three-phase motors:
Table 11- 11 Terminal designations using the example 1U1-1
1
x
11.2.10.4

Direction of rotation

The motors are suitable for clockwise and counter-clockwise rotation.
When the line feeder cables are connected in the phase sequence L1, L2, L3 to U, V, W, the
motor rotates clockwise when looking at the drive end of the shaft extension (DE). If two of
the connections are swapped, the resulting direction of rotation is counter-clockwise,
e.g. L1, L2, L3 to V, U, W.
380
Fixing in the terminal box
U
1
-
1
Designation
Index showing the pole assignment for pole-changing three-phase motors
(lower number = lower speed)
or, in special cases, for a subdivided winding
x
Phase designation (U, V, W)
x
Index showing winding start (1)
Index showing winding end (2)
Additional indexes if there is more than one connection per winding
x
Additional indices if it is obligatory to connect parallel line feeder cables to
several terminals with otherwise identical designations