Siemens SINAMICS G115D Operating Instructions Manual page 228

Distributed drive
Hide thumbs Also See for SINAMICS G115D:
Table of Contents

Advertisement

Advanced commissioning
6.16 PID technology controller
Parameter
p2271
r2272
PID technology controller, fixed values (binary selection)
Parameter
p2201[0...n]
...
p2215[0...n]
p2216[0...n]
r2224
r2225.0
r2229
PID technology controller, fixed values (direct selection)
Parameter
p2216[0...n]
p2220[0...n]
...
p2223[0...n]
r2224
r2225.0
r2229
PID technology controller, motorized potentiometer
Parameter
r2231
p2235[0...n]
226
Description
Technology controller actual value
inversion
CO: Technology controller actual
value scaled [%]
Description
CO: Technology controller fixed
value 1 ... 15 [%]
Technology controller fixed value
selection method
CO: Technology controller fixed
value active [%]
CO/BO: Technology controller
fixed value selection status word
[%]
Technology controller number
actual
Description
Technology controller fixed value
selection method
BI: Technology controller fixed
value selection bit 0 ... 3
CO: Technology controller fixed
value active [%]
CO/BO: Technology controller
fixed value selection status word
[%]
Technology controller number
actual
Description
Technology controller motorized
potentiometer setpoint memory
[%]
BI: Technology controller motor-
ized potentiometer, setpoint, raise
Setting
Setting to invert the actual value signal of the
technology controller.
0: No inversion (Factory setting)
1: Inversion actual value signal
Display and connector output for the scaled actual
value signal of the technology controller.
Setting
Sets the value for fixed value 1 ... 15 of the tech-
nology controller.
Factory setting: 10, 20, 30 ... 150
Sets the method to select the fixed setpoints:
1: Direct selection (factory setting)
2: Binary selection
Display and connector output for the selected and
active fixed value of the technology controller.
Display and BICO output for the status word of
the fixed value selection of the technology con-
troller.
Displays the number of the selected fixed setpoint
of the technology controller.
Setting
Sets the method to select the fixed setpoints:
1: Direct selection (factory setting)
2: Binary selection
Sets the signal source to select a fixed value of
the technology controller.
Factory setting: 0
Display and connector output for the selected and
active fixed value of the technology controller.
Display and BICO output for the status word of
the fixed value selection of the technology con-
troller.
Displays the number of the selected fixed setpoint
of the technology controller.
Setting
Displays the setpoint memory for the motorized
potentiometer of the technology controller.
Sets the signal source to continually increase the
setpoint for the motorized potentiometer of the
technology controller.
Factory setting: 0
Operating Instructions, 09/2020, FW V4.7 SP13, A5E48681219B
SINAMICS G115D distributed drive

Advertisement

Table of Contents
loading