Advanced commissioning
6.3 Adapt the default settings of the inputs and outputs
6.3.2

Digital Inputs

Changing the function of the digital inputs
Parameterized as digital inputs
1)
Binector inputs (BI) of the converter
BI
p0810 Command data set selection CDS bit 0
p0840 ON/OFF1
p0844 OFF2
p0848 OFF3
p0852 Enable operation
p0855 Unconditionally release holding brake
p0856 Enable speed controller
p0858 Unconditionally close holding brake
p1020 Fixed speed setpoint selection bit 0
p1021 Fixed speed setpoint selection bit 1
p1022 Fixed speed setpoint selection bit 2
p1023 Fixed speed setpoint selection bit 3
p1035 Motorized potentiometer, setpoint, raise
A complete list of the binector inputs is provided in the List Manual.
Example
106
Significance
Interconnect the status parameter of the digital
input with a binector input of your choice.
Interconnecting signals in the converter
(Page 501)
Binector inputs are marked with "BI" in the parame-
ter list of the List Manual.
BI
Significance
p1036 Motorized potentiometer, setpoint, lower
p1055 Jog bit 0
p1056 Jog bit 1
p1113 Setpoint inversion
p1201 Flying restart enable signal source
p2103 1st acknowledge faults
p2106 External fault 1
p2112 External alarm 1
p2200 Technology controller enable
p3330 Two-wire/three-wire control, control
command 1
p3331 Two-wire/three-wire control, control
command 2
p3332 Two-wire/three-wire control, control
command 3
In order to switch on the motor with digital input DI 2,
you have to connect the status parameter of DI 2 to
p0840: Set p0840 = 722.2.
Operating Instructions, 09/2020, FW V4.7 SP13, A5E48681219B