SRX5800 Services Gateway Grounding Cable Specifications

128

Figure 68: SRX5800 Services Gateway Chassis Grounding Points

M6 (Metric)
Grounding Point
To ground the services gateway, you must connect a grounding cable to earth ground
and then attach it to the chassis grounding point using the two screws provided.
NOTE:
Additional grounding is provided to an AC-powered services gateway
when you plug its power supplies into grounded AC power receptacles.
Grounding the SRX5800 Services Gateway on page 220
SRX5800 Services Gateway Grounding-Cable Lug Specification on page 129
SRX5800 Services Gateway Grounding Cable Specifications on page 128
The grounding cable that you provide must meet the specifications in

Table 40: Grounding Cable Specifications

Cable Type
Grounding
WARNING:
To meet safety and electromagnetic interference (EMI)
requirements and to ensure proper operation, you must properly ground the
1/4-20 Grounding Point
Quantity and Specification
2
One 6-AWG (13.3 mm
), minimum 60°C wire, or as required by
the local code
Copyright © 2015, Juniper Networks, Inc.
Table 40 on page
128.