DC Power Cable Lug Specifications for the SRX5600 Services Gateway

The accessory box shipped with the services gateway includes the cable lugs that attach to the terminal
studs of each power supply (see
Figure 20: DC Power Cable Lug
End view
0.28
diameter
0.55
each hole
0.08
0.25
0.625
CAUTION:
attach a cable lug to the grounding and power cables that you supply. A cable with an
incorrectly attached lug can damage the services gateway.
WARNING:
access location. It has a separate protective earthing terminal [Metric -M6 and English
- ¼-20 screw) ground lugs] provided on the chassis. This separate protective earth
terminal must be permanently connected to earth.

DC Power Circuit Breaker Requirements for the SRX5600 Services Gateway

Each DC power supply has a single DC input (–48 VDC and return) that requires a dedicated facility circuit
breaker. We recommend that you use a customer site circuit breaker rated for 40 A (–48 VDC) minimum
for each DC power supply, or as required by local code. Doing so enables you to operate the services
gateway in any configuration without upgrading the power infrastructure.
If you plan to operate a DC-powered services gateway at less than the maximum configuration and do
not provision a 40 A (–48 VDC) circuit breaker, we recommend that you provision a circuit breaker for
each DC power supply rated for at least 125% of the continuous current that the system draws at –48 VDC,
or as required by local code.
Figure 20 on page
59).
2.25
Crimp area
All measurements in inches
0.37
Before services gateway installation begins, a licensed electrician must
The services gateway is a pluggable type A equipment installed in restricted
6 AWG conductor
59