1.7 H: Terminal Functions

1.7

H: Terminal Functions

H parameters assign functions to the external terminals.
u

H1: Multi-Function Digital Inputs

n
H1-01 to H1-07: Functions for Terminals S1 to S7
These parameters assign functions to the multi-function digital inputs. The various functions and settings are listed in
1.28.
No.
H1-01
Multi-Function Digital Input Terminal S1 Function Selection
H1-02
Multi-Function Digital Input Terminal S2 Function Selection
H1-03
Multi-Function Digital Input Terminal S3 Function Selection
H1-04
Multi-Function Digital Input Terminal S4 Function Selection
H1-05
Multi-Function Digital Input Terminal S5 Function Selection
H1-06
Multi-Function Digital Input Terminal S6 Function Selection
H1-07
Multi-Function Digital Input Terminal S7 Function Selection
<1> Number appearing in parenthesis is the default value after performing a 3-Wire initialization.
Setting
0
3-Wire Sequence
3
Multi-Step Speed Reference 1
4
Multi-Step Speed Reference 2
6
Jog reference Selection
7
Accel/Decel Time Selection 1
8
Baseblock Command (N.O.)
9
Baseblock Command (N.C.)
A
Accel/Decel Ramp Hold
B
Drive Overheat Alarm (oH2)
C
Analog Terminal Input Selection
F
Through Mode
10
Up Command
11
Down Command
12
Forward Jog
13
Reverse Jog
14
Fault Reset
15
Fast Stop (N.O.)
17
Fast Stop (N.C.)
18
Timer Function Input
19
PID Disable
1B
Program Lockout
1E
Reference Sample Hold
20 to 2F
External Fault
30
PID Integral Reset
31
PID Integral Hold
34
PID Soft Starter Cancel
35
PID Input Level Selection
40
Forward Run Command (2-Wire sequence)
41
Reverse Run Command (2-Wire sequence)
72
Parameter Name
Table 1.28 Multi-Function Digital Input Terminal Settings
Function
Setting
Range
1 to B2
40 (F)
1 to B2
41 (F)
0 to B2
24: External Fault
0 to B2
14: Fault Reset
<1>
0 to B2
3 (0)
<1>
0 to B2
4 (3)
<1>
0 to B2
6 (4)
Page
Setting
73
42
Run Command (2-Wire sequence 2)
43
FWD/REV Command (2-Wire sequence 2)
73
44
Offset Frequency 1
73
45
Offset Frequency 2
74
46
Offset Frequency 3
47
Node Setup
74
49
GF1 Error (N.O., N.C.)
74
4A
74
50
Motor Pre-Heat 2
74
51
Sequence Timer Disable
74
52
Sequence Timer Cancel
60
Motor Pre-Heat 1
75
61
External Speed Search Command 1
62
External Speed Search Command 2
76
63
Field Weakening
76
65
KEB Ride-Thru 1 (N.C.)
76
66
KEB Ride-Thru 1 (N.O.)
76
67
Communications Test Mode
76
68
High Slip Braking
77
69
Jog 2
77
6A
Drive Enabled
77
6D
AUTO Mode Select
77
6E
HAND Mode Select
78
70
Drive Enable2
78
7A
KEB Ride-Thru 2 (N.C.)
78
7B
KEB Ride-Thru 2 (N.O.)
78
7C
Short Circuit Braking (N.O.)
7D
Short Circuit Braking (N.C.)
78
A4
Emergency Override
A5
BP Drive/Bypass Selection
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual
Default
<1>
: Forward Run Command (2-Wire sequence)
<1>
: Reverse Run Command (2-Wire sequence)
: Multi-Step Speed Reference 1
: Multi-Step Speed Reference 2
: Jog Reference Selection
Function
Table
Page
78
79
79
79
79
79
79
79
79
79
79
80
80
80
80
80
80
80
81
81
81
81
81