14.Click the "Generate" button in the area on the right.
Result: The new process tags that you have defined along with the set values (input
parameters) are read in and displayed (read only).
15.Confirm all settings in the dialog with OK.
Result
These process tags are available for use in the transitions during recipe creation. If the
"S7_measval" or "S7_archive" attribute is set for the parameters and the interconnection to
the WinCC archive is established for the "Process variables" assigned to the units, they can
be used in the "Process tags" tab for batch reports during recipe creation.
Note
If the attribute "S7_m_c = true" is not set for the input of the TAG_COLLECT function block,
the output of the interconnected block is used if the output has the attribute "S7_m_c = true".
7.1.6.3

Second option: Create CFC chart and compile it as a block type

Procedure
1. In the Component view of the SIMATIC Manager, create a new CFC chart below a chart
folder by selecting the menu command Insert > Insert new object > CFC.
2. Select the CFC chart and select the menu command Edit > Open Object.
3. Open the I/O table with View > Chart Inputs/Outputs.
4. Here, you can edit all the values that will be collected as measured values as input
parameters under IN.
SIMATIC BATCH V8.2
Operating Manual, 02/2016, A5E35958174-AA
Engineering
7.1 Basic engineering for PCS 7
167