Step 4: Restoring and inserting project(s) in the CMP

Introduction
In this step, you integrate the project back into the CMP.
Requirements
● You have received the project of the DMP as an archive file.
● No changes were made to the master data library.
Procedure
1. If there is already a project with the same name in the destination path of the CMP, delete it.
In the SIMATIC Manager > File > Delete > User Projects tab > select project > OK > Yes
OK.
2. Retrieve the project in the destination path of the CMP.
In the SIMATIC Manager > File > Retrieve > select archive > Open > select destination
directory > OK > OK > Yes > Yes.
Note
Warning dialog "Retrieve". Do you want to remove the references to this multiproject? Yes.
3. Delete the S7 connection for communication between AS and OS you have configured for
testing.
Open NetPro > Select the CPU in the AS > Select the previously inserted S7 connection >
Shortcut menu > Delete.
Note
If have changed the AS addresses of existing S7 connections, the addresses of the original
CMP must be set again.
4. Remove the BATCH process cell identifier (ISA-88 type definition) and delete the "Batch
process cell" object.
– In the Plant view, select the folder of the batch process cell in your project, right-click
– Select the project in the Plant view > select the batch process cell in the data window >
5. You should run the following checks.
Did you remove the project from the CMP earlier?
Were all the Batch IDs removed first?
Is the name of the top hierarchy folder the same in all projects?
Does the MAC address of the AS match the CMP settings?
236
and select the shortcut menu command "Object properties > In the "S88 type definition"
tab select "<neutral>" > OK. The light green batch identifier is removed in the folder icon.
select > Delete in the shortcut menu > OK.