Preparing The Configuration - Innominate mGuard Reference Manual

Table of Contents

Advertisement

mGuard rs4000/rs2000
20
Innominate Security Technologies
1.4

Preparing the configuration

1.4.1
Connection requirements
The mGuard rs4000/rs2000 must be connected to at least one active power supply
unit.
For local configuration: The computer that is to be used for configuration must be
connected to the LAN socket on the mGuard.
For remote configuration: The mGuard must be configured so that remote configura-
tion is permitted.
The mGuard must be connected, i.e., the required connections must be working.
1.4.2
Local configuration on startup (EIS)
As of firmware version 7.2, initial startup of mGuard products provided in Stealth mode is
considerably easier. From this version onwards, the EIS (Easy Initial Setup) procedure en-
ables startup to be performed via preset or user-defined management addresses without
actually having to connect to an external network.
The mGuard is configured using a web browser on the computer used for configuration.
NOTE: The web browser used must support SSL encryption (i.e., HTTPS).
According to the default setting, the mGuard can be accessed via the following addresses:
Table 1-3
Preset addresses
Default setting
mGuard rs4000
mGuard rs2000
The mGuard is preset to the "multiple Clients" stealth configuration. You need to configure
a management IP address and default gateway if you want to use VPN connections (see
Page 24). Alternatively, you can select a different stealth configuration or use another net-
work mode.
Network mode
Management IP #1
Stealth
https://1.1.1.1/
Stealth
https://1.1.1.1/
Management IP #2
https://192.168.1.1/
https://192.168.1.1/
I15007_en_02

Advertisement

Table of Contents
loading

Table of Contents