Analog Input Modules; Channel Analog Input Modules; Table 87: 1 Channel Analog Input Modules; Table 88: 2 Channel Analog Input Modules - WAGO -I/O-IPC-C6 Manual

Wago-i/o-system 750
Hide thumbs Also See for WAGO-I/O-IPC-C6:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
758-874/000-110 WAGO-I/O-IPC-C6
Pos: 60.6 /Serie 750 (WAGO-I/O-SYSTEM)/Prozessabbild Mapping/ETHERNET - EtherNet/IP - MODBUS/TCP/PA ETHERNET - AIs-Einleitung MODBUS/TCP (INTEL, mit word-alignment) @ 7\mod_1272352811572_21.doc @ 55815 @ 3 @ 1
17.2.3

Analog Input Modules

The hardware of an analog input module has 16 bits of measured analog data per
channel and 8 bits of control/status.
However, the coupler/controller with MODBUS/TCP does not have access to the
8 control/status bits.
Therefore, the coupler/controller with MODBUS/TCP can only access the 16 bits
of analog data per channel, which are grouped as words and mapped in Intel
format in the Input Process Image.
Pos: 60.7 /Serie 750 (WAGO-I/O-SYSTEM)/Prozessabbild Mapping/Sofern in dem Knoten auch Digitaleingangsklemmen gesteckt, zu AIs @ 8\mod_1279112061364_21.doc @ 59903 @ @ 1
When digital input modules are also present in the node, the analog input data is
always mapped into the Input Process Image in front of the digital data.
Pos: 60.8 /Serie 750 (WAGO-I/O-SYSTEM)/Prozessabbild Mapping/Information - Informationen zum Steuer-/Statusbyteaufbau @ 4\mod_1238055708743_21.doc @ 29070 @ @ 1
Information to the structure of the Control/Status byte
For detailed information about the structure of a particular module's control/status
byte, please refer to that module's manual. Manuals for each module can be found
on the Internet under: http://www.wago.com.
Pos: 60.9 /Serie 750 (WAGO-I/O-SYSTEM)/Prozessabbild Mapping/ETHERNET - EtherNet/IP - MODBUS/TCP/PA ETHERNET - AIs (Intel, mit word-alignment) @ 7\mod_1272352054685_21.doc @ 55790 @ 444 @ 1
17.2.3.1

1 Channel Analog Input Modules

750-491, (and all variations)

Table 87: 1 Channel Analog Input Modules

Input Process Image
Offset
0
1
17.2.3.2
2 Channel Analog Input Modules
750-452, -454, -456, -461, -462, -465, -466, -467, -469, -472, -474, -475, 476, -
477, -478, -479, -480, -481, -483, -485, -492, (and all variations),
753-452, -454, -456, -461, -465, -466, -467, -469, -472, -474, -475, 476, -477,
478, -479, -483, -492, (and all variations)

Table 88: 2 Channel Analog Input Modules

Input Process Image
Offset
0
1
Manual
Version 2.3.0
Byte Destination
High Byte
D1
D3
Byte Destination
High Byte
D1
D3
Low Byte
D0
D2
Low Byte
D0
Measured Value Channel 1
D2
Measured Value Channel 2
I/O Modules
195
Description
Measured Value U
D
Measured Value U
ref
Description

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents