Figure 6-40:Input Register Setting Example For Modbus Rtu Module - ICP DAS USA WISE-2841M Series User Manual

Hide thumbs Also See for WISE-2841M Series:
Table of Contents

Advertisement

ICP DAS WISE User Manual
Figure 6-40 shows an example about Input Register setting for a
Modbus RTU module. The starting Modbus address of the Input
Register block is
Input Register data in the setting, and the data type is "32-bit
Floating Point". So that the WISE can access the 30010, 30012 and
30014 Input Register address of the module, and these retrieved
Input Register data will be kept in WISE Modbus Address 34500、
34502 and 34504.
Figure 6-40:Input Register Setting Example for Modbus RTU module
 To modify the starting address or quantity setting, please click on
the setting block to perform the modification. The user could also
modify Type, Scale Ratio and Offset on this interface. The Scale
Ratio setting and Offset setting allows to transform the Input
Register value in this block by linear transformation. The formula is
as follow:
After the linear transformation, the Transformed Value will be saved
in floating point format on the WISE (no matter what format the raw
Input Register value was in the device). The default Scale Ratio will
be 1 and the default Offset is 0, indicating not using linear
transformation.
http://wise.icpdas.com
30010(30000
Transformed Value = Scale Ratio x Input Register value + Offset
+ 10), it requires to set 3 continuous