Figure 6-31:ICP DAS Modbus RTU module DI Channel Setting page
The settings are as below:
 Nickname: For user to define nickname for the module and the
 Description: The Description field provides a space for the user
 Address: The address will be the Modbus address of this module,
 Scan Rate: Input the time interval for WISE to periodically
 Polling Timeout: The time interval for WISE to send command to
 Retry Interval: The time interval to wait for WISE to repeatedly
http://wise.icpdas.com
I/O channels, these nicknames will be displayed on the "Channel
Status" and "Rule Setting" pages.
to make a brief description of this module.
please make sure the address is the same as the settings of the
module, if the setting is not accurate, the connection for WISE to
the Modbus RTU module will be failed.
retrieve the I/O channel data of this module, the setting range will
be 0 ~ 65535 seconds.
the module and wait for the response, the unit will be ms. The
setting range will be 1-10000 ms.
send command again when WISE sends command to the module
and get no response. The unit will be second. The setting range
will be 3 ~ 65535 seconds.