Command
Parameters
Response
http://wise.icpdas.com
job=get_channel_val&
if_type=val&com_port=val&module_no=val&
ch_type=val&ch_addr=val
Name
if_type
Description The type of I/O Interface
Value
0: XV-Board
1: COM Port
2: Ethernet
Name
com_port
Description If the I/O interface is XV-Board or
Ethernet, skip this parameter. If
the I/O interface is COM Port, it is
for the COM Port number.
Value
0: COM0
1: COM1
...so on.
Name
module_no
Description The index number of the module.
Value
Integer; start from 1.
Name
ch_type
Description The channel type
Modbus Module:ci, co, ri, ro
Value
Other Modules:di, dic, do, ai, ao
Name
ch_addr
Description The channel address
Value
The ch_addr is Modbus Data Address
for the Modbus module. For other
module, the ch_addr is the channel
sequence number starting from 0.
The channel is existed.
{