iii In the "Timeout" field, input the time interval for WISE to send
command to the DCON module and wait for the response, the unit
will be millisecond (ms).
iv In the "Checksum" field, specify the Checksum setting for the
communication between WISE and DCON module to be enabled
or disabled.
v After all settings are completed, click "Save" button to save the
changes.
Please Note: Use the DCON Utility to complete the setting of each
DCON modules which will connect with the WISE first. These
setting also must be the same with the setting of WISE.
 Modbus RTU Master (Connect to Modbus RTU slave devices)
Figure 5-27:COM Port Interface Setting for Modbus RTU Master
The settings steps are as below:
i In the "Baudrate" field, select the Baudrate from the dropdown list,
the Baudrate of WISE and Modbus RTU slave module have to be
set the same.
ii In the "Parity" and "Stop bits" fields, set up the Parity and Stop
bits. The Parity and Stop bits of WISE and Modbus RTU slave
module have to be set the same.
iii In the "Silent Interval" field, input the time interval between
successive sending of commands from the WISE to the Modbus
RTU slave module, the unit will be millisecond (ms).
iv After all settings are completed, click "Save" button to save the
changes.