Serial port
  Command line
1. Select the device in Remote Manager and click Actions > Open Console, or log into the IX10
local command line as a user with full Admin access rights.
Depending on your device configuration, you may be presented with an Access selection
menu. Type admin to access the Admin CLI.
2. At the command line, type config to enter configuration mode:
> config
(config)>
3. The serial port is enabled by default. To disable:
(config)> serial port1 enable false
(config)>
4. Set the mode:
(config)> serial port1 mode modbus
(config)>
5. Set the signaling interface type used on this serial port:
rs-232
n
rs-485
n
l
The default is rs-232.
6. (Optional) Set a label that will be used when referring to this port.
(config)>path-paramlabel label
(config)>
7. Expand Serial Settings.
The entries in the following fields must match the information for the power controller. Refer
to your power controller manual for the correct entries.
a. Baud rate: For Baud rate, select the baud rate used by the device to which you want to
connect. The default is 9600.
IX10 User Guide
Enable termination if you want to enable electrical termination on this serial port:
(config)> serial port1 termination true
(config)>
Configure Modbus mode
193