Default parameter settings for the PID control macro

Below is a listing of default parameter values that differ from those listed for the
Factory macro in
Parameter listing
Parameter
No.
Name
12.30 AI2 scaled at AI2 max
19.11
Ext1/Ext2 selection
20.01 Ext1 commands
20.04 Ext1 in2 source
20.06 Ext2 commands
20.08 Ext2 in1 source
20.12 Run enable 1 source
22.12 Speed ref2 source
22.14 Speed ref1/2 selection
22.22 Constant speed sel1
23.11
Ramp set selection
31.11
Fault reset selection
40.07 Set 1 PID operation mode
40.08 Set 1 feedback 1 source
40.11
Set 1 feedback filter time
40.16 Set 1 setpoint 1 source
40.35 Set 1 derivation filter time
(page 91).
PID control macro default
1500.000
DI3
In1 Start
Not selected
In1 Start
DI6
DI5
PID
Follow Ext1/Ext2 selection
DI4
Acc/Dec time 1
Not selected
On
AI2 scaled
0.040 s
AI1 scaled
1.0 s
Application macros 77