Maintenance Timer & Counter - ABB ACS880 Firmware Manual

Primary control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
32.26
Supervision 3
action
No action
Warning
Fault
32.27
Supervision 3
signal
32.28
Supervision 3 filter
time
0.000 ... 30.000 s
32.29
Supervision 3 low
-21474830.00 ...
21474830.00
32.30
Supervision 3 high
-21474830.00 ...
21474830.00
33
33 Maintenance timer &
counter
33.01
Counter status
Bit
Name
0
On-time1
1
On-time2
2
Edge 1
3
Edge 2
4
Value 1
5
Value 2
6...15
Reserved
0000h...FFFFh
33.10
On-time 1 actual
0...4294967295 s
Description
Selects the action the drive takes when the value monitored
by signal supervision 3 exceeds its limits.
Note: This parameter does not affect the status indicated by
32.01 Supervision
status.
No action taken.
A warning
(A8B0 Signal
The drive trips on
80B0 Signal
Selects the signal to be monitored by signal supervision
function 3.
For the available selections, see parameter
Supervision 1
signal.
Defines a filter time constant for the signal monitored by
signal supervision 3.
Signal filter time.
Defines the lower limit for signal supervision 3.
Low limit.
Defines the upper limit for signal supervision 3.
Upper limit.
Configuration of maintenance timers/counters.
See also section
Maintenance timers and counters
Displays the maintenance timer/counter status word,
indicating which maintenance timers/counters have exceeded
their limits.
This parameter is read-only.
Description
1 = On-time timer 1 has reached its preset limit.
1 = On-time timer 2 has reached its preset limit.
1 = Signal edge counter 1 has reached its preset limit.
1 = Signal edge counter 2 has reached its preset limit.
1 = Value counter 1 has reached its preset limit.
1 = Value counter 2 has reached its preset limit.
Maintenance time/counter status word.
Actual present value of on-time timer 1.
The timer runs whenever the signal selected by parameter
33.13 On-time 1 source
When the timer exceeds the limit set by
limit, bit 0 of
33.01 Counter status
specified by
33.14 On-time 1 warn message
enabled by
33.12 On-time 1
The timer can be reset from the Drive composer PC tool, or
from the control panel by keeping Reset depressed for over 3
seconds.
Actual present value of on-time timer 1.
supervision) is generated.
supervision.
32.07
is on.
33.11 On-time 1 warn
is set to 1. The warning
is also given if
function.
Parameters 205
Def/FbEq16
No action
0
1
2
Zero
0.000 s
1000 = 1 s
0.00
-
0.00
-
(page 67).
-
1 = 1
-
-