ABB ACS880 Firmware Manual page 186

Primary control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

186 Parameters
No.
Name/Value
28.32
Constant frequency
7
-500.00 ... 500.00
Hz
28.41
Frequency ref safe
-500.00 ... 500.00
Hz
28.51
Critical frequency
function
Bit
Name
0
Enable
1
Sign mode
0000h...FFFFh
28.52
Critical frequency 1
low
-500.00 ... 500.00
Hz
28.53
Critical frequency 1
high
-500.00 ... 500.00
Hz
28.54
Critical frequency 2
low
-500.00 ... 500.00
Hz
28.55
Critical frequency 2
high
-500.00 ... 500.00
Hz
28.56
Critical frequency 3
low
-500.00 ... 500.00
Hz
Description
Defines constant frequency 7.
Constant frequency 7.
Defines a safe frequency reference value that is used with
supervision functions such as
12.03 AI supervision function
49.05 Communication loss action
• 50.02 FBA A comm loss func
50.32 FBA B comm loss
Safe frequency reference.
Enables/disables the critical frequencies function. Also
determines whether the specified ranges are effective in both
rotating directions or not.
See also section
Critical speeds/frequencies
Information
1 = Enable: Critical frequencies enabled.
0 = Disable: Critical frequencies disabled.
1 = According to par: The signs of parameters
into account.
0 = Absolute: Parameters
Each range is effective in both directions of rotation.
Critical frequencies configuration word.
Defines the low limit for critical frequency 1.
Note: This value must be less than or equal to the value of
28.53 Critical frequency 1
Low limit for critical frequency 1.
Defines the high limit for critical frequency 1.
Note: This value must be greater than or equal to the value of
28.52 Critical frequency 1
High limit for critical frequency 1.
Defines the low limit for critical frequency 2.
Note: This value must be less than or equal to the value of
28.55 Critical frequency 2
Low limit for critical frequency 2.
Defines the high limit for critical frequency 2.
Note: This value must be greater than or equal to the value of
28.54 Critical frequency 2
High limit for critical frequency 2.
Defines the low limit for critical frequency 3.
Note: This value must be less than or equal to the value of
28.57 Critical frequency 3
Low limit for critical frequency 3.
func.
(page 38).
28.52...28.57
are handled as absolute values.
high.
low.
high.
low.
high.
Def/FbEq16
0.00 Hz
See par.
46.02
0.00 Hz
See par.
46.02
00b
28.52...28.57
are taken
1 = 1
0.00 Hz
See par.
46.02
0.00 Hz
See par.
46.02
0.00 Hz
See par.
46.02
0.00 Hz
See par.
46.02
0.00 Hz
See par.
46.02

Advertisement

Table of Contents
loading