ABB ACS880 Firmware Manual page 129

Primary control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
14.49
AI2 max
-22.000 ... 22.000
mA or V
14.50
AI2 scaled at AI2
min
-32768.000 ...
32767.000
14.51
AI2 scaled at AI2
max
-32768.000 ...
32767.000
14.56
AI3 actual value
-22.000 ... 22.000
mA or V
14.57
AI3 scaled value
-32768.000 ...
32767.000
14.58
AI3 force data
-22.000 ... 22.000
mA or V
Description
(Visible when
14.01 Module 1 type
Defines the maximum value for analog input AI2.
Maximum value of AI2.
(Visible when
14.01 Module 1 type
Defines the real value that corresponds to the minimum
analog input AI2 value defined by parameter
14.42
14.51
14.48
Real value corresponding to minimum AI2 value.
(Visible when
14.01 Module 1 type
Defines the real value that corresponds to the maximum
analog input AI2 value defined by parameter
See the drawing at parameter
Real value corresponding to maximum AI2 value.
(Visible when
14.01 Module 1 type
Displays the value of analog input AI3 in mA or V (depending
on whether the input is set to current or voltage).
This parameter is read-only.
Value of analog input AI3.
(Visible when
14.01 Module 1 type
Displays the value of analog input AI3 after scaling. See
parameter
14.65 AI3 scaled at AI3
This parameter is read-only.
Scaled value of analog input AI3.
(Visible when
14.01 Module 1 type
Forced value that can be used instead of the true reading of
the input. See parameter
Forced value of analog input AI3.
= FIO-11)
= FIO-11)
14.48 AI2
14.49
14.50
= FIO-11)
14.49 AI2
14.50 AI2 scaled at AI2
= FIO-11)
= FIO-11)
min.
= FIO-11)
14.22 AI force
selection.
Parameters 129
Def/FbEq16
10.000 mA or
V
1000 = 1 mA
or V
0.000
min.
14.41
1 = 1
100.000
max.
min.
1 = 1
-
1000 = 1 mA
or V
-
1 = 1
0.000 mA
1000 = 1 mA
or V