Parameter Listing; Actual Values - ABB ACS880 Firmware Manual

Primary control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

Parameter listing

No.
Name/Value
01

01 Actual values

01.01
Motor speed used
-30000.00 ...
30000.00 rpm
01.02
Motor speed
estimated
-30000.00 ...
30000.00 rpm
01.04
Encoder 1 speed
filtered
-30000.00 ...
30000.00 rpm
01.05
Encoder 2 speed
filtered
-30000.00 ...
30000.00 rpm
01.06
Output frequency
-500.00 ... 500.00
Hz
01.07
Motor current
0.00 ... 30000.00 A
01.10
Motor torque %
-1600.0 ... 1600.0% Motor torque.
01.11
DC voltage
0.00 ... 2000.00 V
01.13
Output voltage
0...2000 V
01.14
Output power
-32768.00 ...
32767.00 kW or hp
Description
Basic signals for monitoring the drive.
All parameters in this group are read-only unless otherwise
noted.
Measured or estimated motor speed depending on which
type of feedback is used (see parameter
feedback
selection). A filter time constant for this signal can
be defined by parameter
Measured or estimated motor speed.
Estimated motor speed in rpm. A filter time constant for this
signal can be defined by parameter
speed.
Estimated motor speed.
Speed of encoder 1 in rpm. A filter time constant for this
signal can be defined by parameter
speed.
Encoder 1 speed.
Speed of encoder 2 in rpm.A filter time constant for this signal
can be defined by parameter
Encoder 2 speed.
Estimated drive output frequency in Hz. A filter time constant
for this signal can be defined by parameter
output
frequency.
Estimated output frequency.
Measured (absolute) motor current in A.
Motor current.
Motor torque in percent of the nominal motor torque. See also
parameter
01.30 Nominal torque
A filter time constant for this signal can be defined by
parameter
46.13 Filter time motor
Measured DC link voltage.
DC link voltage.
Calculated motor voltage in V AC.
Motor voltage.
Drive output power. The unit is selected by parameter
Unit
selection. A filter time constant for this signal can be
defined by parameter
46.14 Filter time power
Output power.
90.41 Motor
46.11 Filter time motor
speed.
46.11 Filter time motor
46.11 Filter time motor
46.11 Filter time motor
46.12 Filter time
scale.
torque.
out.
Parameters 91
Def/FbEq16
-
See par.
46.01
-
See par.
46.01
-
See par.
46.01
-
speed.
See par.
46.01
-
See par.
46.02
-
1 = 1 A
-
See par.
46.03
-
10 = 1 V
-
1 = 1 V
96.16
-
1 = 1 unit

Advertisement

Table of Contents
loading

Table of Contents