Process Pid Set 1 - ABB ACS880 Firmware Manual

Primary control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
36.43
AL2 30 to 40%
0.00 ... 100.00%
36.44
AL2 40 to 50%
0.00 ... 100.00%
36.45
AL2 50 to 60%
0.00 ... 100.00%
36.46
AL2 60 to 70%
0.00 ... 100.00%
36.47
AL2 70 to 80%
0.00 ... 100.00%
36.48
AL2 80 to 90%
0.00 ... 100.00%
36.49
AL2 over 90%
0.00 ... 100.00%
36.50
AL2 reset date
-
36.51
AL2 reset time
-
40

40 Process PID set 1

40.01
Process PID output
actual
-32768.00 ...
32767.00
Description
Percentage of samples recorded by amplitude logger 2 that
fall between 30 and 40%.
Amplitude logger 2 samples between 30 and 40%.
Percentage of samples recorded by amplitude logger 2 that
fall between 40 and 50%.
Amplitude logger 2 samples between 40 and 50%.
Percentage of samples recorded by amplitude logger 2 that
fall between 50 and 60%.
Amplitude logger 2 samples between 50 and 60%.
Percentage of samples recorded by amplitude logger 2 that
fall between 60 and 70%.
Amplitude logger 2 samples between 60 and 70%.
Percentage of samples recorded by amplitude logger 2 that
fall between 70 and 80%.
Amplitude logger 2 samples between 70 and 80%.
Percentage of samples recorded by amplitude logger 2 that
fall between 80 and 90%.
Amplitude logger 2 samples between 80 and 90%.
Percentage of samples recorded by amplitude logger 2 that
exceed 90%.
Amplitude logger 2 samples over 90%.
The date on which amplitude logger 2 was last reset.
Last reset date of amplitude logger 2.
The time at which amplitude logger 2 was last reset.
Last reset time of amplitude logger 2.
Parameter values for process PID control.
The drive contains a single active PID controller for process
use, however two separate complete set-ups can be
programmed and stored.
The first set is made up of parameters 40.07...40.56*, the
second set is defined by the parameters in group
PID set
2. The binary source that defines which set is used is
selected by parameter
40.57 PID set1/set2
See also the control chain diagrams on pages
*The remaining parameters in this group are common for both
sets.
Displays the output of the process PID controller. See the
control chain diagram on page 404.
This parameter is read-only. The unit is selected by
parameter
40.12 Set 1 unit
Process PID controller output.
41 Process
selection.
403
selection.
Parameters 225
Def/FbEq16
0.00%
1 = 1%
0.00%
1 = 1%
0.00%
1 = 1%
0.00%
1 = 1%
0.00%
1 = 1%
0.00%
1 = 1%
0.00%
1 = 1%
-
-
-
-
and 404.
-
1 = 1 unit