ABB ACS880 Firmware Manual page 356

Primary control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

356 Fault tracing
Code
Warning
(hex)
A6E5
AI parametrization
A780
Motor stall
Programmable warning:
31.24 Stall function
A781
Motor fan
Programmable warning:
35.106 DOL starter event
type
A782
FEN temperature
A791
Brake resistor
A793
BR excess
temperature
A794
BR data
A797
Speed feedback
configuration
A79B
BC short circuit
Cause
The current/voltage hardware
setting of an analog input does
not correspond to parameter
settings.
Motor is operating in stall
region because of e.g.
excessive load or insufficient
motor power.
No feedback received from
external fan.
Error in temperature
measurement when
temperature sensor (KTY or
PTC) connected to encoder
interface FEN-xx is used.
Error in temperature
measurement when KTY
sensor connected to encoder
interface FEN-01 is used.
Brake resistor broken or not
connected.
Brake resistor temperature has
exceeded warning limit defined
by parameter
43.12 Brake
resistor warning
limit.
Brake resistor data has not
been given.
Speed feedback configuration
has changed.
Short circuit in brake chopper
IGBT
What to do
Check the event log for an auxiliary code.
The code identifies the analog input
whose settings are in conflict.
Adjust either the hardware setting (on the
drive control unit) or parameter
12.15/12.25.
Note: Control board reboot (either by
cycling the power or through parameter
96.08 Control board
boot) is required to
validate any changes in the hardware
settings.
Check motor load and drive ratings.
Check fault function parameters.
Check external fan (or other equipment
controlled) by the logic.
Check settings of parameters
35.100...35.106.
Check that parameter
35.11 Temperature
1 source
/
35.21 Temperature 2 source
setting corresponds to actual encoder
interface installation.
FEN-01 does not support temperature
measurement with KTY sensor. Use PTC
sensor or other encoder interface
module.
Check that a brake resistor has been
connected.
Check the condition of the brake resistor.
Stop drive. Let resistor cool down.
Check resistor overload protection
function settings (parameter group
Brake
chopper).
Check warning limit setting, parameter
43.12 Brake resistor warning
Check that the resistor has been
dimensioned correctly.
Check that braking cycle meets allowed
limits.
Check the resistor data settings
(parameters 43.08...43.10).
Use parameter
91.10 Encoder parameter
refresh) to validate any changes in the
settings.
Replace brake chopper if external. Drives
with internal choppers will need to be
returned to ABB.
Ensure brake resistor is connected and
not damaged.
43
limit.

Advertisement

Table of Contents
loading

Table of Contents