Selection of constant speeds
By default, constant speeds 1...7 are selected using digital inputs DI4...DI6 as
follows:
DI4
DI5
DI6
0
0
0
1
0
0
0
1
0
1
1
0
0
0
1
1
0
1
0
1
1
1
1
1
Default parameter settings for the Sequential control macro
Below is a listing of default parameter values that differ from those listed for the
Factory macro in
Parameter listing
Parameter
No.
Name
21.03 Stop mode
22.21 Constant speed function
22.22 Constant speed sel1
22.23 Constant speed sel2
22.24 Constant speed sel3
22.27 Constant speed 2
22.28 Constant speed 3
22.29 Constant speed 4
22.30 Constant speed 5
22.31 Constant speed 6
22.32 Constant speed 7
23.11
Ramp set selection
25.06 Acc comp derivation time
31.11
Fault reset selection
Constant speed active
None (External speed
reference used)
Constant speed 1
Constant speed 2
Constant speed 3
Constant speed 4
Constant speed 5
Constant speed 6
Constant speed 7
(page 91).
Sequential control macro
default
Ramp
01b (Bit 0 = Packed)
DI4
DI5
DI6
600.00 rpm
900.00 rpm
1200.00 rpm
1500.00 rpm
2400.00 rpm
3000.00 rpm
DI3
0.12 s
Not selected
Application macros 83