304 Parameters
No.
Name/Value
99.07
Motor nominal
voltage
0.0 ... 800.0
99.08
Motor nominal
frequency
0.0 ... 500.0 Hz
99.09
Motor nominal
speed
0 ... 30000 rpm
99.10
Motor nominal
power
-10000.00 ...
10000.00 kW or
-13404.83 ...
13404.83 hp
99.11
Motor nominal cosfii
0.00 ... 1.00
99.12
Motor nominal
torque
0.000...
N·m or lb·ft
Description
Defines the nominal motor voltage supplied to the motor. This
setting must match the value on the rating plate of the motor.
Notes:
• With permanent magnet motors, the nominal voltage is the
BackEMF voltage at nominal speed of the motor. If the
voltage is given as voltage per rpm, e.g. 60 V per 1000
rpm, the voltage for a nominal speed of 3000 rpm is
3 × 60 V = 180 V. Note that the nominal voltage is not
equal to the equivalent DC motor voltage (EDCM)
specified by some motor manufacturers. The nominal
voltage can be calculated by dividing the EDCM voltage by
1.7 (or square root of 3).
• The stress on the motor insulation is always dependent on
the drive supply voltage. This also applies to the case
where the motor voltage rating is lower than that of the
drive and the supply.
• This parameter cannot be changed while the drive is
running.
Nominal voltage of the motor.
Defines the nominal motor frequency. This setting must
match the value on the rating plate of the motor.
Note: This parameter cannot be changed while the drive is
running.
Nominal frequency of the motor.
Defines the nominal motor speed. The setting must match the
value on the rating plate of the motor.
Note: This parameter cannot be changed while the drive is
running.
Nominal speed of the motor.
Defines the nominal motor power. The setting must match the
value on the rating plate of the motor. If multiple motors are
connected to the drive, enter the total power of the motors.
The unit is selected by parameter
Note: This parameter cannot be changed while the drive is
running.
Nominal power of the motor.
Defines the cosphi of the motor for a more accurate motor
model. (Not applicable to permanent magnet motors.) Not
obligatory; if set, should match the value on the rating plate of
the motor.
Note: This parameter cannot be changed while the drive is
running.
Cosphi of the motor.
Defines the nominal motor shaft torque for a more accurate
motor model. Not obligatory. The unit is selected by
parameter
96.16 Unit
selection.
Note: This parameter cannot be changed while the drive is
running.
Nominal motor torque.
96.16 Unit
selection.
Def/FbEq16
0.0 V
10 = 1 V
50.0 Hz
10 = 1 Hz
0 rpm
1 = 1 rpm
0.00 kW or
hp
1 = 1 unit
0.00
100 = 1
0.000
N·m or lb·ft
1 = 100 unit