No.
Name/Value
35.102 DOL starter off
delay
0...715828 min
35.103 DOL starter
feedback source
Not selected
Selected
DI1
DI2
DI3
DI4
DI5
DI6
DIO1
DIO2
Other [bit]
35.104 DOL starter
feedback delay
0...42949673 s
Description
Defines a stop delay for the motor fan.
The delay timer starts when the control source selected by
parameter
35.100
switches off. After the delay, bit 1 of
switches off.
Motor fan stop delay.
Selects the input for motor fan feedback signal.
0 = Stopped
1 = Running
After the fan is started (bit 1 of
is expected within the time set by 35.104.
0.
1.
Digital input DI1
(10.02 DI delayed
Digital input DI2
(10.02 DI delayed
Digital input DI3
(10.02 DI delayed
Digital input DI4
(10.02 DI delayed
Digital input DI5
(10.02 DI delayed
Digital input DI6
(10.02 DI delayed
Digital input/output DIO1
Digital input/output DIO2
Source selection (see
Terms and abbreviations
Defines a feedback delay for the motor fan.
The delay timer starts when bit 1 of
feedback is received from the fan until the delay elapses, the
action selected by
35.106
Note: This delay is only applied at start. If the feedback signal
is lost during run, the action selected by
immediately.
Motor fan start delay.
35.105
switches on), feedback
status, bit 0).
status, bit 1).
status, bit 2).
status, bit 3).
status, bit 4).
status, bit 5).
(11.02 DIO delayed
status, bit 0).
(11.02 DIO delayed
status, bit 1).
on page 88).
35.105
switches on. If no
is taken.
35.106
is taken
Parameters 221
Def/FbEq16
20 min
35.105
1 = 1 min
Not selected
0
1
2
3
4
5
6
7
10
11
-
0 s
1 = 1 s