No.
Name/Value
40.36
Set 1 output min
-32768.0 ...
32767.0
40.37
Set 1 output max
-32768.0 ...
32767.0
40.38
Set 1 output freeze
enable
Not selected
Selected
DI1
DI2
DI3
DI4
DI5
DI6
DIO1
DIO2
Other [bit]
Description
Defines the minimum limit for the process PID controller
output. Using the minimum and maximum limits, it is possible
to restrict the operation range.
Minimum limit for process PID controller output.
Defines the maximum limit for the process PID controller
output. See parameter
40.36 Set 1 output
Maximum limit for process PID controller output.
Freezes (or defines a source that can be used to freeze) the
output of the process PID controller, keeping the output at the
value it was before freeze was enabled. This feature can be
used when, for example, a sensor providing process
feedback must to be serviced without stopping the process.
1 = Process PID controller output frozen
See also parameter
40.30 Set 1 setpoint freeze
Process PID controller output not frozen.
Process PID controller output frozen.
Digital input DI1
(10.02 DI delayed
Digital input DI2
(10.02 DI delayed
Digital input DI3
(10.02 DI delayed
Digital input DI4
(10.02 DI delayed
Digital input DI5
(10.02 DI delayed
Digital input DI6
(10.02 DI delayed
Digital input/output DIO1
Digital input/output DIO2
Source selection (see
Terms and abbreviations
min.
enable.
status, bit 0).
status, bit 1).
status, bit 2).
status, bit 3).
status, bit 4).
status, bit 5).
(11.02 DIO delayed
status, bit 0).
(11.02 DIO delayed
status, bit 1).
on page 88).
Parameters 233
Def/FbEq16
-32768.0
1 = 1
32767.0
1 = 1
Not selected
0
1
2
3
4
5
6
7
10
11
-