ABB ACS880 Firmware Manual page 300

Primary control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

300 Parameters
No.
Name/Value
97.11
TR tuning
25...400%
97.13
IR compensation
0.00 ... 50.00%
97.15
Motor model
temperature
adaptation
No
Yes
Description
Rotor time constant tuning.
This parameter can be used to improve torque accuracy in
closed-loop control of an induction motor. Normally, the motor
identification run provides sufficient torque accuracy, but
manual fine-tuning can be applied in exceptionally
demanding applications to achieve optimal performance.
Note: This is an expert level parameter and should not be
adjusted without appropriate skill.
Rotor time constant tuning.
Defines the relative output voltage boost at zero speed (IR
compensation). The function is useful in applications with a
high break-away torque where direct torque control (DTC
mode) cannot be applied.
U / U
N
(%)
Relative output voltage. IR
compensation set to 15%.
100%
15%
Field weakening point
50% of nominal
frequency
See also section
IR compensation for scalar motor control
page 45.
Voltage boost at zero speed in percent of nominal motor
voltage.
Selects whether the temperature-dependent parameters
(such as stator or rotor resistance) of the motor model adapt
to actual (measured or estimated) temperature or not.
Temperature adaptation of motor model disabled.
Temperature adaptation of motor model enabled.
Relative output voltage. No
IR compensation.
f (Hz)
Def/FbEq16
100%
1 = 1%
0.00%
on
1 = 1%
No
0
1

Advertisement