Contents of the fieldbus Control word

The upper case boldface text refers to the states shown in the state diagram (page
383).
Bit
Name
0
Off1 control
1
Off2 control
2
Off3 control
3
Run
4
Ramp out zero
5
Ramp hold
6
Ramp in zero
7
Reset
8
Inching 1
9
Inching 2
10
Remote cmd
11
Ext ctrl loc
12 to 15 Reserved.
Fieldbus control through a fieldbus adapter 381
Value STATE/Description
1
Proceed to READY TO OPERATE.
0
Stop along currently active deceleration ramp. Proceed to OFF1
ACTIVE; proceed to READY TO SWITCH ON unless other interlocks
(OFF2, OFF3) are active.
1
Continue operation (OFF2 inactive).
0
Emergency OFF, coast to a stop.
Proceed to OFF2 ACTIVE, proceed to SWITCH-ON INHIBITED.
1
Continue operation (OFF3 inactive).
0
Emergency stop, stop within time defined by drive parameter.
Proceed to OFF3 ACTIVE; proceed to SWITCH-ON INHIBITED.
WARNING: Ensure motor and driven machine can be
stopped using this stop mode.
1
Proceed to OPERATION ENABLED.
Note: Run enable signal must be active; see drive documentation. If
the drive is set to receive the Run enable signal from the fieldbus, this
bit activates the signal.
0
Inhibit operation. Proceed to OPERATION INHIBITED.
1
Normal operation. Proceed to RAMP FUNCTION GENERATOR:
OUTPUT ENABLED.
0
Force Ramp function generator output to zero. The drive will
immediately decelerate to zero speed (observing the torque limits).
1
Enable ramp function.
Proceed to RAMP FUNCTION GENERATOR: ACCELERATOR
ENABLED.
0
Halt ramping (Ramp Function Generator output held).
1
Normal operation. Proceed to OPERATING.
Note: This bit is effective only if the fieldbus interface is set as the
source for this signal by drive parameters.
0
Force Ramp function generator input to zero.
0=>1
Fault reset if an active fault exists. Proceed to SWITCH-ON
INHIBITED.
Note: This bit is effective only if the fieldbus interface is set as the
source of the reset signal by drive parameters.
0
Continue normal operation.
1
Accelerate to inching (jogging) setpoint 1.
Notes:
• Bits 4...6 must be 0.
• See also section
0
Inching (jogging) 1 disabled.
1
Accelerate to inching (jogging) setpoint 2.
See notes at bit 8.
0
Inching (jogging) 2 disabled.
1
Fieldbus control enabled.
0
Control word and reference not getting through to the drive, except
for bits 0...2.
1
Select External Control Location EXT2. Effective if control location is
parameterized to be selected from fieldbus.
0
Select External Control Location EXT1. Effective if control location is
parameterized to be selected from fieldbus.
Jogging
(page 41).