Load Analyzer - ABB ACS880 Firmware Manual

Primary control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

222 Parameters
No.
Name/Value
35.105 DOL starter status
word
Bit
Name
0
Start command
1
Delayed start
command
2
DOL feedback
3
DOL fault (-1)
4...15
Reserved
0000h...FFFFh
35.106 DOL starter event
type
No action
Warning
Fault
36

36 Load analyzer

36.01
PVL signal source
Not selected
Motor speed used
Output frequency
Motor current
Motor torque
Dc-voltage
Power inu out
Speed ref ramp in
Description
Status of the motor fan control logic.
Bit 1 is the control output for the fan, to be selected as the
source of, for example, a digital or relay output.
The other bits indicate the statuses of the selected control
and feedback sources, and the fault status.
This parameter is read-only.
Description
Status of fan control source selected by 35.100.
0 = Stop requested
1 = Start requested
Fan control bit (delays observed). Select this bit as the source of the
output controlling the fan.
0 = Stopped
1 = Started
Status of fan feedback (source selected by 35.103).
0 = Stopped
1 = Running
Fault status.
0 = Fault (fan feedback missing). The action taken is selected by
35.106.
1 = No fault
Status of motor fan control logic.
Selects the action taken when missing fan feedback is
detected by the motor fan control logic.
No action taken.
The drive generates a warning
Drive trips on
71B1 Motor
Peak value and amplitude logger settings.
See also section
Load analyzer
Selects the signal to be monitored by the peak value logger.
The signal is filtered using the filtering time specified by
parameter
36.02 PVL filter
The peak value is stored, along with other pre-selected
signals at the time, into parameters 36.10...36.15.
The peak value logger can be reset using parameter
Reset
loggers. The date and time of the last reset are stored
into parameters
36.16
and
None (peak value logger disabled).
01.01 Motor speed used
01.06 Output frequency
01.07 Motor current
(page 91).
01.10 Motor torque %
(page 91).
01.11 DC voltage
(page 91).
01.14 Output power
(page 91).
23.01 Speed ref ramp input
(A781 Motor
fan).
fan.
(page 68).
time.
36.17
respectively.
(page 91).
(page 91).
(page 164).
Def/FbEq16
-
1 = 1
Fault
0
1
2
Power inu
out
36.09
0
1
3
4
6
7
8
10