Monitoring/Scaling Settings - ABB ACS880 Firmware Manual

Primary control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
DI5
DI6
DIO1
DIO2
Other [bit]
45.17
Tariff currency unit
Local currency
EUR
USD
45.18
CO2 conversion
factor
0.000 ... 65.535
tn/MWh
45.19
Comparison power
0.0 ... 100000.0 kW Motor power.
45.21
Energy calculations
reset
Done
Reset
46
46 Monitoring/scaling
settings
46.01
Speed scaling
0.10 ... 30000.00
rpm
Description
Digital input DI5
(10.02 DI delayed
Digital input DI6
(10.02 DI delayed
Digital input/output DIO1
Digital input/output DIO2
Source selection (see
Terms and abbreviations
Specifies the currency used for the savings calculations.
The currency is determined by the language selection (see
parameter
96.01
Language).
Euro.
US dollar.
Defines a factor for conversion of saved energy into CO
emissions (kg/kWh or tn/MWh).
Factor for conversion of saved energy into CO
Actual power that the motor absorbs when connected direct-
on-line and operating the application. The value is used for
reference when energy savings are calculated.
Note: The accuracy of the energy savings calculation is
directly dependent on the accuracy of this value. If nothing is
entered here, then the nominal motor power is used by the
calculation, but that may inflate the energy savings reported
as many motors do not absorb nameplate power.
Resets the savings counter parameters 45.01...45.09.
Reset not requested (normal operation), or reset complete.
Reset the savings counter parameters. The value reverts
automatically to Done.
Speed supervision settings; actual signal filtering; general
scaling settings.
Defines the maximum speed value used to define the
acceleration ramp rate and the initial speed value used to
define the deceleration ramp rate (see parameter group
Speed reference
ramp). The speed acceleration and
deceleration ramp times are therefore related to this value
(not to parameter
30.12 Maximum
Also defines the 16-bit scaling of speed-related parameters.
The value of this parameter corresponds to 20000 in fieldbus,
master/follower etc. communication.
Acceleration/deceleration terminal/initial speed.
status, bit 4).
status, bit 5).
(11.02 DIO delayed
status, bit 0).
(11.02 DIO delayed
status, bit 1).
on page 88).
emissions.
2
speed).
Parameters 247
Def/FbEq16
6
7
10
11
-
EUR
100
101
102
0.500
2
tn/MWh
1 = 1 tn/MWh
0.0 kW
1 = 1 kW
Done
0
1
1500.00 rpm
23
1 = 1 rpm