130 Parameters
No.
Name/Value
14.59
AI3 HW switch
position
V
mA
14.60
AI3 unit selection
V
mA
14.61
AI3 filter gain
No filtering
125 us
250 us
500 us
1 ms
2 ms
4 ms
7.9375 ms
Description
(Visible when
14.01 Module 1 type
Shows the position of the hardware current/voltage selector
on the I/O extension module.
Note: The setting of the current/voltage selector must match
the unit selection made in parameter
I/O module reboot either by cycling the power or through
parameter
96.08 Control board boot
any changes in the hardware settings.
Volts.
Milliamperes.
(Visible when
14.01 Module 1 type
Selects the unit for readings and settings related to analog
input AI3.
Note: This setting must match the corresponding hardware
setting on the I/O extension module (see the manual of the
I/O extension module). The hardware setting is shown by
parameter
14.59 AI3 HW switch
either by cycling the power or through parameter
Control board boot
is required to validate any changes in the
hardware settings.
Volts.
Milliamperes.
(Visible when
14.01 Module 1 type
Selects a hardware filtering time for AI3.
See also parameter
14.62 AI3 filter
No filtering.
125 microseconds.
250 microseconds.
500 microseconds.
1 millisecond.
2 milliseconds.
4 milliseconds.
7.9375 milliseconds.
= FIO-11)
14.60 AI3 unit
selection.
is required to validate
= FIO-11)
position. I/O module reboot
96.08
= FIO-11)
time.
Def/FbEq16
-
2
10
mA
2
10
No filtering
0
1
2
3
4
5
6
7