Control And Status Words - ABB ACS880 Firmware Manual

Primary control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
05.22
Diagnostic word 3
Bit
Name
0...10
Reserved
11
Fan command
12...15 Reserved
0000h...FFFFh
06
06 Control and status
words
06.01
Main control word
0000h...FFFFh
06.02
Application control
word
0000h...FFFFh
06.03
FBA A transparent
control word
00000000h ...
FFFFFFFFh
06.04
FBA B transparent
control word
00000000h ...
FFFFFFFFh
06.11
Main status word
0000h...FFFFh
Description
Diagnostic word 3.
Value
1 = Drive fan is rotating above idle speed
Diagnostic word 3.
Drive control and status words.
The main control word of the drive. This parameter shows the
control signals as received from the selected sources (such
as digital inputs, the fieldbus interface and the application
program).
The bit assignments of the word are as described on page
381. The related status word and state diagram are presented
on pages
382
and
383
respectively.
Note: Bits 12...15 can be used to carry additional control
data, and used as a signal source by any binary-source
selector parameter.
This parameter is read-only.
Main control word.
The drive control word received from the application program
(if any). The bit assignments are described on page 381.
This parameter is read-only.
Application program control word.
The unaltered control word received from the PLC through
fieldbus adapter A.
This parameter is read-only.
Control word received through fieldbus adapter A.
The unaltered control word received from the PLC through
fieldbus adapter B.
This parameter is read-only.
Control word received through fieldbus adapter B.
Main status word of the drive.
The bit assignments are described on page 382. The related
control word and state diagram are presented on pages
and
383
respectively.
This parameter is read-only.
Main status word.
Parameters 95
Def/FbEq16
-
1 = 1
-
1 = 1
-
1 = 1
-
-
-
1 = 1
-
381
1 = 1

Advertisement

Table of Contents
loading

Table of Contents