262 Parameters
No.
Name/Value
51.29
FBA A drive type
code
0...65535
51.30
FBA A mapping file
ver
0...65535
51.31
D2FBA A comm
status
Not configured
Initializing
Time out
Configuration error
Off-line
On-line
Reset
51.32
FBA A comm SW
ver
51.33
FBA A appl SW ver
52

52 FBA A data in

52.01
FBA A data in1
None
CW 16bit
Ref1 16bit
Ref2 16bit
SW 16bit
Act1 16bit
Act2 16bit
Description
Displays the drive type code in the fieldbus adapter module
mapping file (stored in the memory of the drive).
This parameter is read-only.
Drive type code stored in the mapping file.
Displays the fieldbus adapter module mapping file revision
stored in the memory of the drive in decimal format.
This parameter is read-only.
Mapping file revision.
Displays the status of the fieldbus adapter module
communication.
Adapter is not configured.
Adapter is initializing.
A timeout has occurred in the communication between the
adapter and the drive.
Adapter configuration error: mapping file not found in the file
system of the drive, or mapping file upload has failed more
than three times.
Fieldbus communication is off-line.
Fieldbus communication is on-line, or fieldbus adapter has
been configured not to detect a communication break. For
more information, see the documentation of the fieldbus
adapter.
Adapter is performing a hardware reset.
Displays the common program revision of the adapter module
in format axyz, where a = major revision number, xy = minor
revision number, z = correction number or letter.
Example: 190A = revision 1.90A.
Common program revision of adapter module.
Displays the application program revision of the adapter
module in format axyz, where a = major revision number, xy =
minor revision number, z = correction number or letter.
Example: 190A = revision 1.90A.
Application program version of adapter module.
Selection of data to be transfered from drive to fieldbus
controller through fieldbus adapter A.
Note: 32-bit values require two consecutive parameters.
Whenever a 32-bit value is selected in a data parameter, the
next parameter is automatically reserved.
Parameters
52.01...52.12
the drive to the fieldbus controller through fieldbus adapter A.
None.
Control Word (16 bits)
Reference REF1 (16 bits)
Reference REF2 (16 bits)
Status Word (16 bits)
Actual value ACT1 (16 bits)
Actual value ACT2 (16 bits)
select data to be transfered from
Def/FbEq16
-
1 = 1
-
1 = 1
-
0
1
2
3
4
5
6
-
-
None
0
1
2
3
4
5
6