ABB ACS880 Firmware Manual page 207

Primary control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
33.21
On-time 2 warn limit
0...4294967295 s
33.22
On-time 2 function
Bit
Function
0
Counter mode
0 = Loop: When the limit is reached, the counter is reset. The counter status (bit 1 of
33.01) switches to 1 for one second. The warning (if enabled) stays active for at least 10
seconds.
1 = Saturate: When the limit is reached, the counter status (bit 1 of 33.01) switches to 1,
and remains so until
is reset.
1
Warning enable
0 = Disable: No warning is given when the limit is reached
1 = Enable: A warning (see 33.24) is given when the limit is reached
2...15
Reserved
0000h...FFFFh
33.23
On-time 2 source
False
True
RO1
Other [bit]
33.24
On-time 2 warn
message
On-time 2
exceeded
Clean device
Maintain additional
cool fan
Maintain cabinet
fan
Maintain DC
capacitors
Maintain motor
bearing
Description
Sets the warning limit for on-time timer 2.
Warning limit for on-time counter 2.
Configures on-time timer 2.
33.20
is reset. The warning (if enabled) also stays active until
On-time timer 2 configuration word.
Selects the signal to be monitored by on-time timer 2.
Constant 0 (timer disabled).
Constant 1.
Bit 0 of
10.21 RO status
Source selection (see
Terms and abbreviations
Selects the optional warning message for on-time timer 2.
A887 On-time
2. The message text can be edited on the
control panel by choosing Menu – Settings – Edit texts.
A88C Device
clean.
A890 Additional
cooling.
A88E Cabinet
fan.
A88D DC
capacitor.
A880 Motor
bearing.
(page 105).
on page 88).
Parameters 207
Def/FbEq16
0 s
-
00b
33.20
1 = 1
False
0
1
2
-
On-time 2
exceeded
1
6
7
8
9
10