ABB ACS880 Firmware Manual page 355

Primary control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

Code
Warning
(hex)
A4F6
IGBT temperature
A580
PU communication
A5A0
Safe torque off
Programmable warning:
31.22 STO indication
run/stop
A5EA
Measurement circuit
temperature
A5EB
PU board powerfail
A5EC PU communication
internal
A5ED Measurement circuit
ADC
A5EE
Measurement circuit
DFF
A5EF
PU state feedback
A5F0
Charging feedback
A6A4
Motor nominal value
A6A5
No motor data
A6A6
Supply voltage
unselected
A6D1
FBA A parameter
conflict
A6D2
FBA B parameter
conflict
Cause
Drive IGBT temperature is
excessive.
Communication errors
detected between the drive
control unit and the power unit.
Safe torque off function is
active, i.e. safety circuit
signal(s) connected to
connector XSTO is lost.
Problem with internal
temperature measurement of
the drive.
Power unit power supply
failure.
Communication errors
detected between the drive
control unit and the power unit.
Measurement circuit fault.
Measurement circuit fault.
State feedback from output
phases does not match control
signals.
Charging feedback signal
missing.
The motor parameters are set
incorrectly.
The drive is not dimensioned
correctly.
Parameters in group 99 have
not been set.
The supply voltage has not
been defined.
The drive does not have a
functionality requested by a
PLC, or requested functionality
has not been activated.
The drive does not have a
functionality requested by a
PLC, or requested functionality
has not been activated.
Fault tracing 355
What to do
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against drive power.
Check the connections between the drive
control unit and the power unit.
Check safety circuit connections. For
more information, see appropriate drive
hardware manual and description of
parameter
31.22 STO indication run/stop
(page 198).
Contact your local ABB representative.
Contact your local ABB representative.
Check the connections between the drive
control unit and the power unit.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Check the feedback signal coming from
the charging system.
Check the settings of the motor
configuration parameters in group 99.
Check that the drive is sized correctly for
the motor.
Check that all the required parameters in
group 99 have been set.
Note: It is normal for this warning to
appear during the start-up and continue
until the motor data is entered.
Set supply voltage in parameter
Supply
voltage.
Check PLC programming.
Check settings of parameter groups
Fieldbus adapter (FBA)
settings.
Check PLC programming.
Check settings of parameter groups
Fieldbus adapter (FBA)
settings.
95.01
50
and
51 FBA A
50
and
54 FBA B