226 Parameters
No.
Name/Value
40.02
Process PID
feedback actual
-32768.00 ...
32767.00
40.03
Process PID
setpoint actual
-32768.00 ...
32767.00
40.04
Process PID
deviation actual
-32768.00 ...
32767.00
40.05
Process PID trim
output act
-32768.00 ...
32767.00
40.06
Process PID status
word
Bit
Name
0
PID active
1
Setpoint frozen
2
Output frozen
3
PID sleep mode
4
Sleep boost
5
Trim mode
6
Tracking mode
7
Output limit high
8
Output limit low
9
Deadband active
10
PID set
11
Reserved
12...15 Reserved
0000h...FFFFh
Description
Displays the value of process feedback after source
selection, mathematical function (parameter
feedback
function), and filtering. See the control chain
diagram on page 403.
This parameter is read-only. The unit is selected by
parameter
40.12 Set 1 unit
Process feedback.
Displays the value of process PID setpoint after source
selection, mathematical function
function), limitation and ramping. See the control chain
diagram on page 404.
This parameter is read-only. The unit is selected by
parameter
40.12 Set 1 unit
Setpoint for process PID controller.
Displays the process PID deviation. By default, this value
equals setpoint - feedback, but deviation can be inverted by
parameter
40.31 Set 1 deviation
chain diagram on page 404.
This parameter is read-only. The unit is selected by
parameter
40.12 Set 1 unit
PID deviation.
Displays the trimmed reference output. See the control chain
diagram on page 404.
This parameter is read-only. The unit is selected by
parameter
40.12 Set 1 unit
Trimmed reference.
Displays status information on process PID control.
This parameter is read-only.
Value
1 = Process PID control active.
1 = Process PID setpoint frozen.
1 = Process PID controller output frozen.
1 = Sleep mode active.
1 = Sleep boost active.
1 = Trim function active.
1 = Tracking function active.
1 = PID output is being limited by par. 40.37.
1 = PID output is being limited by par. 40.36.
1 = Deadband active (see par. 40.39)
0 = Parameter set 1 in use. 1 = Parameter set 2 in use.
Process PID control status word.
40.10 Set 1
selection.
(40.18 Set 1 setpoint
selection.
inversion. See the control
selection.
selection.
Def/FbEq16
-
1 = 1 unit
-
1 = 1 unit
-
1 = 1 unit
-
1 = 1 unit
-
1 = 1

Advertisement