ABB ACS880 Firmware Manual page 223

Primary control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
Speed ref ramped
Speed ref used
Torq ref used
Freq ref used
Process PID out
Process PID fbk
Process PID act
Process PID dev
Other
36.02
PVL filter time
0.00 ... 120.00 s
36.06
AL2 signal source
36.07
AL2 signal scaling
0.00 ... 32767.00
36.09
Reset loggers
Done
All
PVL
AL2
36.10
PVL peak value
-32768.00 ...
32767.00
36.11
PVL peak date
-
36.12
PVL peak time
-
36.13
PVL current at peak
-32768.00 ...
32767.00 A
36.14
PVL DC voltage at
peak
0.00 ... 2000.00 V
Description
23.02 Speed ref ramp output
24.01 Used speed reference
26.02 Torque reference used
28.02 Frequency ref ramp output
40.01 Process PID output actual
40.02 Process PID feedback actual
40.03 Process PID setpoint actual
40.04 Process PID deviation actual
Source selection (see
Terms and abbreviations
Peak value logger filtering time. See parameter
signal
source.
Peak value logger filtering time.
Selects the signal to be monitored by amplitude logger 2. The
signal is sampled at 200 ms intervals.
The results are displayed by parameters 36.40...36.49. Each
parameter represents an amplitude range, and shows what
portion of the samples fall within that range.
The signal value corresponding to 100% is defined by
parameter
36.07 AL2 signal
Amplitude logger 2 can be reset using parameter
loggers. The date and time of the last reset are stored into
parameters
36.50
and
36.51
For the selections, see parameter
Defines the signal value that corresponds to 100% amplitude. 100.00
Signal value corresponding to 100%.
Resets the peak value logger and/or amplitude logger 2.
(Amplitude logger 1 cannot be reset.)
Reset completed or not requested (normal operation).
Reset both the peak value logger and amplitude logger 2.
Reset the peak value logger.
Reset amplitude logger 2.
Peak value recorded by the peak value logger.
Peak value.
The date on which the peak value was recorded.
Peak occurrence date.
The time at which the peak value was recorded.
Peak occurrence time.
Motor current at the moment the peak value was recorded.
Motor current at peak.
Voltage in the intermediate DC circuit of the drive at the
moment the peak value was recorded.
DC voltage at peak.
(page 164).
(page 169).
(page 177).
(page 182).
(page 225).
(page 226).
(page 226).
(page 226).
on page 88).
36.01 PVL
scaling.
36.09 Reset
respectively.
36.01 PVL signal
Parameters 223
Def/FbEq16
11
12
13
14
16
17
18
19
-
2.00 s
100 = 1 s
Motor torque
source.
1 = 1
Done
0
1
2
3
0.00
1 = 1
-
-
-
-
0.00 A
1 = 1 A
0.00 V
10 = 1 V