No.
Name/Value
40.07
Set 1 PID operation
mode
Off
On
On when drive
running
40.08
Set 1 feedback 1
source
Not selected
AI1 scaled
AI2 scaled
Freq in scaled
Motor current
Power inu out
Motor torque
Other
40.09
Set 1 feedback 2
source
40.10
Set 1 feedback
function
In1
In1+In2
In1-In2
In1*In2
In1/In2
MIN(In1,In2)
MAX(In1,In2)
AVE(In1,In2)
sqrt(In1)
sqrt(In1-In2)
sqrt(In1+In2)
sqrt(In1)+sqrt(In2)
40.11
Set 1 feedback filter
time
0.000 ... 30.000 s
40.12
Set 1 unit selection
rpm
%
Hz
Description
Activates/deactivates process PID control.
Note: Process PID control is only available in external
control; see section
Local control vs. external control
20).
Process PID control inactive.
Process PID control active.
Process PID control is active when the drive is running.
Selects the first source of process feedback. See the control
chain diagram on page 403.
None.
12.12 AI1 scaled value
(see page 113).
12.22 AI2 scaled value
(see page 114).
11.39 Freq in 1 scaled
(see page 109).
01.07 Motor current
(see page 91).
01.14 Output power
(see page 91).
01.10 Motor torque %
(see page 91).
Source selection (see
Terms and abbreviations
Selects the second source of process feedback.
For the selections, see parameter
source.
Defines how process feedback is calculated from the two
feedback sources selected by parameters
feedback 1 source
and
40.09 Set 1 feedback 2
Source 1.
Sum of sources 1 and 2.
Source 2 subtracted from source 1.
Source 1 multiplied by source 2.
Source 1 divided by source 2.
Smaller of the two sources.
Greater of the two sources.
Average of the two sources.
Square root of source 1.
Square root of (source 1 - source 2).
Square root of (source 1 + source 2).
Square root of source 1 + square root of source 2.
Defines the filter time constant for process feedback.
Feedback filter time.
Defines the unit for parameters 40.01...40.05,
and 40.47.
rpm.
%.
Hz.
Parameters 227
(page
on page 88).
40.08 Set 1 feedback 1
40.08 Set 1
source.
40.21...40.24
Def/FbEq16
Off
0
1
2
AI1 scaled
0
1
2
3
5
6
7
-
Not selected
In1
0
1
2
3
4
5
6
7
8
9
10
11
0.000 s
1 = 1 s
rpm
7
4
3

Advertisement

Table of Contents
loading

Table of Contents