250 Parameters
No.
Name/Value
46.23
At torque hysteresis
0.0 ... 300.0%
46.31
Above speed limit
0.00 ... 30000.00
rpm
46.32
Above frequency
limit
0.00 ... 1000.00 Hz
46.33
Above torque limit
0.0 ... 1600.0%
47

47 Data storage

47.01
Data storage 1
real32
-2147483.008 ...
2147483.008
47.02
Data storage 2
real32
-2147483.008 ...
2147483.008
47.03
Data storage 3
real32
-2147483.008 ...
2147483.008
Description
Defines the "at setpoint" limits for torque control of the drive.
When the absolute difference between reference
Torque reference act
4) and actual torque
torque
%) is smaller than
is considered to be "at setpoint". This is indicated by bit 8 of
06.11 Main status
word.
Drive at setpoint
(06.11
bit 8 = 1)
Limit for "at setpoint" indication in torque control.
Defines the trigger level for "above limit" indication in speed
control. When actual speed exceeds the limit, bit 10 of
Drive status word 2
is set.
"Above limit" indication trigger level for speed control.
Defines the trigger level for "above limit" indication in
frequency control. When actual frequency exceeds the limit,
bit 10 of
06.17 Drive status word 2
"Above limit" indication trigger level for frequency control.
Defines the trigger level for "above limit" indication in torque
control. When actual torque exceeds the limit, bit 10 of
Drive status word 2
is set.
"Above limit" indication trigger level for torque control.
Data storage parameters that can be written to and read from
using other parameters' source and target settings.
Note that there are different storage parameters for different
data types.
See also section
Data storage parameters
Data storage parameter 1.
32-bit data.
Data storage parameter 2.
32-bit data.
Data storage parameter 3.
32-bit data.
(01.10 Motor
46.23 At torque
hysteresis, the drive
01.10
(%)
26.73
+
46.23
(%)
26.73
(%)
26.73
-
46.23
(%)
0 %
is set.
(page 70).
Def/FbEq16
10.0%
(26.73
See par.
46.03
0.00 rpm
06.17
See par.
46.01
0.00 Hz
See par.
46.02
0.0%
06.17
See par.
46.03
0.000
-
0.000
-