No.
Name/Value
DI2
DI3
DI4
DI5
DI6
DIO1
DIO2
Other [bit]
31.12
Autoreset selection
Bit
Fault
0
Overcurrent
1
Overvoltage
2
Undervoltage
3
AI supervision fault
4
Supply unit
5...9
Reserved
10
Selectable fault (see parameter
11
External fault 1 (from source selected by parameter
12
External fault 2 (from source selected by parameter
13
External fault 3 (from source selected by parameter
14
External fault 4 (from source selected by parameter
15
External fault 5 (from source selected by parameter
0000h...FFFFh
31.13
Selectable fault
0...65535
31.14
Number of trials
0...5
31.15
Total trials time
1.0 ... 600.0 s
Description
Digital input DI2
(10.02 DI delayed
Digital input DI3
(10.02 DI delayed
Digital input DI4
(10.02 DI delayed
Digital input DI5
(10.02 DI delayed
Digital input DI6
(10.02 DI delayed
Digital input/output DIO1
Digital input/output DIO2
Source selection (see
Terms and abbreviations
Selects faults that are automatically reset. The parameter is a
16-bit word with each bit corresponding to a fault type.
Whenever a bit is set to 1, the corresponding fault is
automatically reset.
Note: The autoreset function is only available in external
control; see section
Local control vs. external control
20).
The bits of this binary number correspond to the following
faults:
31.13 Selectable
Automatic reset configuration word.
Defines the fault that can be automatically reset using
parameter
31.12 Autoreset
The faults are listed in chapter
Note: The fault codes are in hexadecimal. The selected code
must be converted to decimal for this parameter.
Fault code.
Defines the number of automatic fault resets the drive
performs within the time defined by parameter
trials
time.
Number of automatic resets.
Defines the time the automatic reset function will attempt to
reset the drive. During this time, it will perform the number of
automatic resets defined by
Time for automatic resets.
status, bit 1).
status, bit 2).
status, bit 3).
status, bit 4).
status, bit 5).
(11.02 DIO delayed
status, bit 0).
(11.02 DIO delayed
status, bit 1).
on page 88).
fault)
31.01 External event 1
31.03 External event 2
31.05 External event 3
31.07 External event 4
31.09 External event 5
selection, bit 10.
Fault tracing
(page 363).
31.15 Total
31.14 Number of
trials.
Parameters 197
Def/FbEq16
3
4
5
6
7
10
11
-
0000h
(page
source)
source)
source)
source)
source)
1 = 1
0
10 = 1
0
10 = 1
30.0 s
10 = 1 s