ABB ACS880 Firmware Manual page 361

Primary control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

Code
Warning
(hex)
A88C
Device clean
A88D
DC capacitor
A88E
Cabinet fan
A88F
Cooling fan
A890
Additional cooling
A8A0
AI supervision
Programmable warning:
12.03 AI supervision
function
A8B0
Signal supervision
(Editable message text)
Programmable warning:
32.06 Supervision 1 action
32.16 Supervision 2 action
32.26 Supervision 3 action
A981
External warning 1
(Editable message text)
Programmable warning:
31.01 External event 1
source
31.02 External event 1
type
A982
External warning 2
(Editable message text)
Programmable warning:
31.03 External event 2
source
31.04 External event 2
type
A983
External warning 3
(Editable message text)
Programmable warning:
31.05 External event 3
source
31.06 External event 3
type
A984
External warning 4
(Editable message text)
Programmable warning:
31.07 External event 4
source
31.08 External event 4
type
A985
External warning 5
(Editable message text)
Programmable warning:
31.09 External event 5
source
31.10 External event 5
type
AF8C
Process PID sleep
mode
AFAA
Autoreset
Cause
Warning generated by an on-
time timer.
Programmable warnings:
33.14 On-time 1 warn message
33.24 On-time 2 warn message
An analog signal is outside the
limits specified for the analog
input.
Warning generated by a signal
supervision function.
Fault in external device 1.
Fault in external device 2.
Fault in external device 3.
Fault in external device 4.
Fault in external device 5.
The drive is entering sleep
mode.
A fault is about to be autoreset. Informative warning. See the settings in
Fault tracing 361
What to do
Check the event log for an auxiliary code.
Check the source of the warning
corresponding to the code:
0:
33.13 On-time 1 source
1:
33.23 On-time 2 source
10:
05.04 Fan on-time
counter.
Check signal level at the analog input.
Check the wiring connected to the input.
Check the minimum and maximum limits
of the input in parameter group
Standard
AI.
Check the source of the warning
(parameter 32.07,
32.17
Check the external device.
Check setting of parameter
External event 1
source.
Check the external device.
Check setting of parameter
External event 2
source.
Check the external device.
Check setting of parameter
External event 3
source.
Check the external device.
Check setting of parameter
External event 4
source.
Check the external device.
Check setting of parameter
External event 5
source.
Informative warning. See section
function for process PID control
51), and parameters 40.41...40.48.
parameter group
31 Fault
12
or 32.28).
31.01
31.03
31.05
31.07
31.09
Sleep
(page
functions.