Standard Dio, Fi, Fo - ABB ACS880 Firmware Manual

Primary control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
10.31
RO3 ON delay
Status of selected
source
RO status
t
=
10.31 RO3 ON delay
On
t
=
10.32 RO3 OFF delay
Off
0.0 ... 3000.0 s
10.32
RO3 OFF delay
0.0 ... 3000.0 s
11

11 Standard DIO, FI, FO

11.01
DIO status
0000h...FFFFh
11.02
DIO delayed status
0000h...FFFFh
11.05
DIO1 function
Output
Input
Frequency
11.06
DIO1 output source
Not energized
Energized
Ready run
Enabled
Started
Magnetized
Running
Ready ref
Description
Defines the activation delay for relay output RO3.
t
t
On
Off
Activation delay for RO3.
Defines the deactivation delay for relay output RO3. See
parameter
10.31 RO3 ON
Deactivation delay for RO3.
Configuration of digital input/outputs and frequency
inputs/outputs.
Displays the status of digital input/outputs DIO8...DIO1. The
activation/deactivation delays (if any are specified) are
ignored.
Example: 0000001001b = DIO1 and DIO4 are on, remainder
are off.
This parameter is read-only.
Status of digital input/outputs.
Displays the delayed status of digital input/outputs
DIO8...DIO1. This word is updated only after
activation/deactivation delays (if any are specified).
Example: 0000001001b = DIO1 and DIO4 are on, remainder
are off.
This parameter is read-only.
Delayed status of digital input/outputs.
Selects whether DIO1 is used as a digital output or input, or a
frequency input.
DIO1 is used as a digital output.
DIO1 is used as a digital input.
DIO1 is used as a frequency input.
Selects a drive signal to be connected to digital input/output
DIO1 when parameter
11.05 DIO1 function
Output is off.
Output is on.
Bit 1 of
06.11 Main status word
Bit 0 of
06.16 Drive status word 1
Bit 5 of
06.16 Drive status word 1
Bit 1 of
06.17 Drive status word 2
Bit 6 of
06.16 Drive status word 1
Bit 2 of
06.11 Main status word
t
On
delay.
is set to Output.
(see page 95).
(see page 96).
(see page 96).
(see page 96).
(see page 96).
(see page 95).
Parameters 107
Def/FbEq16
0.0 s
1
0
1
0
Time
t
Off
10 = 1 s
0.0 s
10 = 1 s
-
1 = 1
-
1 = 1
Output
0
1
2
Not
energized
0
1
2
4
5
6
7
8