Contents Of The Fieldbus Control Word - ABB ACS880 Firmware Manual

Diode supply control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

192 Fieldbus control through a fieldbus adapter

Contents of the fieldbus Control word

Bit
Name
0
On/Off
1
Off 2
2
Off 3
3
Start
4
-
5
-
6
-
7
Reset
8
-
9
-
10
Remote
command
11
Ext ctrl loc
12
User bit 0
13
User bit 1
14
User bit 2
15
User bit 3
Value
Description
1
DxT modules: If either ON/OFF (bit 0) or Start (bit 3) is 1:
1. Close the main contactor/breaker and charge the DC busbar.
2. Ready to operate.
0
If both ON/OFF (bit 0) or Start (bit 3) is 0:
Switch off the charging contactor and the main contactor/breaker.
1
Continue operation (OFF2 inactive)
0
Emergency stop, open main contactor
1
Continue operation (OFF3 inactive)
0
Emergency stop, open main contactor
1
DxT modules: If either ON/OFF (bit 0) or Start (bit 3) is 1:
1. Close the main contactor/breaker and charge the DC busbar.
2. Ready to operate.
0
If both Run (bit 0) or Start (bit 3) is 0:
Switch off the charging contactor and the main contactor/breaker.
1
Not in use.
0
Not in use.
1
Not in use.
0
Not in use.
1
Not in use.
0
Not in use.
0=>1
Fault reset if an active fault exists.
0
- (no reset)
1
Not in use.
0
Not in use.
1
Not in use.
0
Not in use.
1
Drive in remote mode, fieldbus control enabled.
0
Drive in local mode, Control word bits 0...7 received and executed
by drive. Control word bits 8...15 and reference 1 and 2 received by
drive but not executed.
1
Select External Control Location EXT2. Effective if control location
is parameterized to be selected from fieldbus.
0
Select External Control Location EXT1. Effective if control location
is parameterized to be selected from fieldbus.
1
User bit 0 from external control location.
0
User bit 0 from external control location.
1
User bit 1 from external control location.
0
User bit 1 from external control location.
1
User bit 2 from external control location.
0
User bit 2 from external control location.
1
User bit 3 from external control location.
0
User bit 3 from external control location.

Advertisement

Table of Contents
loading

Table of Contents