3.2.6
TM31 Terminal Module (option C01)
The option comprises the TM31 Terminal Module. The inputs and outputs are wired as follows:
● The eight digital inputs are wired to X520 and X530.
● The analog outputs are wired to X522.
● The two relay outputs are wired to X542 on the terminal strip.
● The four bidirectional digital inputs and outputs are wired to coupling relays. The coupling
3.2.7
Three SMC30 Sensor Modules (option C02)
In addition to the three SMC30 Sensor Modules, a DMC20 DRIVE-CLiQ hub and an interface
converter are included.
The SMC30 Sensor Module cannot loop through DRIVE-CLiQ wiring. This is the reason that
the DRIVE-CLiQ hub is required. The DRIVE-CLiQ hub collects the signals from the three
34
Actual value output (X70)
A1 load
Digital potentiometer calibration JP1/2
Actual value output (X71)
A2 load
Valve feedback signals
Firing control from the PSA
Signaling firing outputs H13 - H24
Diagnostics connector
Firing outputs (X1)
Overview of interfaces and display elements
relays are also available at the terminal strip with their floating changeover contacts.
⑫
Feedback information of the blocking volt‐
age measurement (X6)
⑬
LED display (from left to right)
● Pulse power supply OK
● -24 V
● +15 V
● Firing pulse inhibit
⑭
+24 V DC power supply,
Pulse power supply monitoring output
⑮
Actual value inputs (X2)
⑯
Signaling firing outputs H1 - H12