Possible error messages – HART® devices to SW-Rev.: 01.03
Range
Displays the
device
status
Electronics
F
Electronics
S
Electronics
F
Electronics
M
Electronics
F
Electronics
I
Installation / Configuration
I
Electronics
I
Electronics
F
Electronics
F
Electronics
F
Installation / Configuration
C
Sensor
F
Sensor
F
Sensor
F
Sensor
F
Sensor
F
Installation / Configuration
I
Installation / Configuration
I
Sensor
F
Sensor
F
Sensor
F
Sensor
F
Sensor
F
Installation / Configuration
F
Displays the
Cause
DIAG.NO.
1
Device defective
2
Ambient temperature overshot / undershot
3
EEPROM defective
4
Electronics overload
5
Memory error
7
LCD display connected
8
Device write-protected
9
EEPROM busy
12
Sensor input defective (communication)
13
Sensor input defective (error)
14
Sensor input defective (ADC error)
32
Simulation mode
34
Measuring error, sensor 1
35
Short-circuit, sensor 1
36
Wire break, sensor 1
37
Range exceeded, sensor 1
38
Range undershot, sensor 1
41
Single-point adjustment active, sensor 1
42
Two-point adjustment active, sensor 1
50
Measuring error, sensor 2
51
Short-circuit, sensor 2
52
Wire break, sensor 2
53
Range exceeded, sensor 2
54
Range undershot, sensor 2
65
Configuration defective
Remedy
Replace the device
Check environment; reposition measuring point if
required
Replace the device
Factory reset
Factory reset
Remove display
Remove write protection
Wait for status information to finish processing
Replace the device
Replace the device
Replace the device
Exit simulation mode
Check sensor connection
Check sensor connection
Check sensor connection
Check measuring limits
Check measuring limits
Terminate single-point adjustment
Terminate two-point adjustment
Check sensor connection
Check sensor connection
Check sensor connection
Check measuring limits
Check measuring limits
Check configuration:
A Wrong device
B Measuring span is too small
C Incorrect configuration data