Fieldbus Description
Enable switching the DC output on and off
Bit 3 enables or disables the control of the output via cyclic process data.
Bit 3
1
0
Overload behavior
Bits 6 ... 9 control the overload behavior.
Bit 6
1
0
0
0
Latching after thermal overload
Bit 12 controls the latching shutdown in case of thermal overload.
Bit 12
1
0
Boost behavior
Bits 13 and 14 control the boost behavior.
Bit 13
0
0
1
1

4.2.4.8 Configuration of digital input (Index 424)

Enable switching DC output on/off via DI
Bit 0 enables switching on and off the output of the power supply. A LOW level at the DI
means that the output is switched on. A HIGH level at the DI means that the output is
switched off.
Bit 0
1
0
24
| Version: 1.1.0
Communication Module IO-Link
Table 30: Enable switching the DC output on and off via cyclic process data
IODD Value
active
inactive
Bit 7
Bit 8
Bit 9
IODD Value
0
0
0
Constant current
1
0
0
Constant current (latching mode)
0
1
0
Hiccup mode
0
0
1
Electronic circuit breaker
IODD Value
active
inactive
Bit 14
0
1
0
1
IODD Value
active
inactive
Description
enabled
disabled
Table 31: Overload behavior
Description
Constant current
Constant current with latching shut-
down
Hiccup mode
Electronic circuit breaker
Table 32: Latching after thermal overload
Description
enabled
disabled
Table 33: Boost Behavior
IODD Value
Description
No Boost
Boost disabled
TopBoost
TopBoost enabled
PowerBoost
PowerBoost enabled
PowerBoost + TopBoost
TopBoost and PowerBoost
enabled
Table 34: Enable switching DC output on/off via DI
Description
enabled
disabled
2789-9080