Messages And Events; Error Messages For Wago Power Supplies Pro 2; Events And Measured Values For Wago Power Supply Pro 2 - WAGO 2789-9080 Product Manual

Communication modules, communication module io-link
Hide thumbs Also See for 2789-9080:
Table of Contents

Advertisement

2789-9080
Disable reset to factory settings
Bit 7 locks or unlocks the reset to factory settings.
Bit 7
1
0

4.3 Messages and Events

4.3.1 Error Messages for WAGO Power Supplies Pro 2

Index
(Hex.)
0x8000
0x8011
0x8012
0x8023
0x8030
0x8033
0x8035
0x8036
0x8040
0x8041
0x8158
1)
Read Only
2)
Cyclic redundancy check

4.3.2 Events and Measured Values for WAGO Power Supply Pro 2

Index Bit
1539
| Version: 1.1.0
Communication Module IO-Link
IODD Value
active
inactive
Error Message
Device application error – no details
Index not available
Subindex not available
Access denied – Index not writeable
Parameter value out of range
Parameter length overrun
Function not available
Function temporarily unavailable
Invalid parameter set
Inconsistent parameter set
Password protection active
Events – Warning
No.
0
Output under-voltage
1
outOverVoltage
2
OutputOverLoad
3
outOverLoadCustom
4
opHoursLimitReached
5
powerBoostActive
6
topBoostActive
7
highTemperature
8
diEvent
Table 46: Disable reset to factory settings
Description
Unsupported function
Parameters not available on this index.
Subindex not available
Write access to RO
Limiting value overrun
Invalid parameter length, structure error, CRC
error
Writing an invalid value to command parameter.
Command not possible due to current command
status (e.g., during block parameterization that is
not closed; other commands are rejected).
Written parameter value does not match the cur-
rent configuration.
Plausibility check of the block parameterization
failed.
No parameter access; password protection en-
abled
Description
Undervoltage at output below DC OK threshold
Overvoltage: +10 % of the set output voltage
Overload present
Configurable overload threshold has been exceeded.
Configurable operating hours have been reached.
PowerBoost output, information is visible for 5 seconds.
TopBoost output, information is visible for 5 seconds.
High device temperature
Event on DI is present.
Fieldbus Description
Description
enabled
disabled
Table 47: Error Messages
1)
parameter
Table 48: Events – Warnings
2)
27

Advertisement

Table of Contents
loading

Table of Contents