Parameters 5-** Digital In/Out - Danfoss VLT AQUA Drive FC 200 Programming Manual

Hide thumbs Also See for VLT AQUA Drive FC 200:
Table of Contents

Advertisement

Parameter Description

3.7 Parameters 5-** Digital In/Out

Parameter group for configuring the digital input and
output.
3
3
3.7.1 5-0* Digital I/O Mode
Parameters for configuring the input and output using
NPN and PNP.
5-00 Digital I/O Mode
Option:
[0] PNP - Active
at 24 V
[1] NPN - Active
at 0V
NOTICE!
This parameter cannot be adjusted while the motor is
running.
5-01 Terminal 27 Mode
Option:
[0]
Input
[1]
Output
NOTICE!
This parameter cannot be adjusted while the motor is
running.
5-02 Terminal 29 Mode
Option:
[0]
Input
[1]
Output
NOTICE!
This parameter cannot be adjusted while the motor is
running.
3.7.2 5-1* Digital Inputs
Parameters for configuring the input functions for the
input terminals.
The digital inputs are used for selecting various functions
in the adjustable frequency drive. All digital inputs can be
set to the following functions:
3-42
VLT
Function:
Digital inputs and programmed digital
outputs are pre-programmable for operation
either in PNP or NPN systems.
Action on positive directional pulses (0). PNP
systems are pulled down to GND.
Action on negative directional pulses (1).
NPN systems are pulled up to +24 V,
internally in the adjustable frequency drive.
Function:
Defines terminal 27 as a digital input.
Defines terminal 27 as a digital output.
Function:
Defines terminal 29 as a digital input.
Defines terminal 29 as a digital output.
MG20O622 - VLT
®
AQUA Drive Programming Guide
Digital input function
No operation
Reset
Coast inverse
Coast and reset inverse
DC brake inverse
Stop inverse
External interlock
Start
Latched start
Reversing
Start reversing
Jog
Preset reference on
Preset ref bit 0
Preset ref bit 1
Preset ref bit 2
Freeze reference
Freeze output
Speed up
Slow
Set-up select bit 0
Set-up select bit 1
Pulse input
Ramp bit 0
Mains failure inverse
Hand/Auto Start
Run Permissive
Hand start
Auto start
DigiPot increase
DigiPot decrease
DigiPot Clear
Counter A (up)
Counter A (down)
Reset Counter A
Counter B (up)
Counter B (down)
Reset Counter B
Sleep Mode
Reset Maintenance Word
PTC Card 1
Latched Pump Derag
Lead Pump Start
Lead Pump Alternation
Pump 1 Interlock
Pump 2 Interlock
Pump 3 Interlock
Table 3.11
®
is a registered Danfoss trademark
Select
Terminal
[0]
All *term 32, 33, 29, 19
[1]
All
[2]
All * term 27
[3]
All
[5]
All
[6]
All
[7]
All
[8]
All
[9]
All
[10]
All
[11]
All
[14]
All
[15]
All
[16]
All
[17]
All
[18]
All
[19]
All
[20]
All
[21]
All
[22]
All
[23]
All
[24]
All
[32]
term 29, 33
[34]
All
[36]
All
[51]
All
[52]
All
[53]
All
[54]
All
[55]
All
[56]
All
[57]
All
[60]
29, 33
[61]
29, 33
[62]
All
[63]
29, 33
[64]
29, 33
[65]
All
[66]
All
[78]
All
[80]
All
[85]
All
[120]
All
[121]
All
[130]
All
[131]
All
[132]
All

Advertisement

Table of Contents
loading